Note: See chapter SPS 362 of the building code for stretcher-sized elevator requirements in some commercial buildings.
SPS 318.1702(8)
(8)
Car and counterweight safeties. This is a department rule in addition to the requirements in ASME A17.1 section 2.17.14: The manufacturer's model number shall also be marked on the metal plate.
SPS 318.1702(9)
(9)
Speed governors. This is a department rule in addition to the requirements in ASME A17.1 section 2.18.9: The manufacturer's model number shall also be marked on the metal plate.
SPS 318.1702(10)(a)
(a) Emergency or standby power system. This is a department informational note to be used under ASME A17.1 section 2.27.2:
Note: Standby power requirements for elevators in healthcare facilities are found in Article 517 of the National Electrical Code®, as adopted under chapter SPS 316. In other types of commercial buildings, stand-by power requirements are found in the building code under IBC chapter 27.
SPS 318.1702(10)(b)1g.1g. This is a department informational note to be used under ASME A17.1 section 2.27.3.2.1:
SPS 318.1702 Note
Note: Where a conflict between NFPA 13 and NFPA 72 occurs relating to this section, the department will refer to NFPA 13.
SPS 318.1702(10)(b)1r.
1r. Substitute the following wording for the requirements in ASME A17.1 section 2.27.3.2.3 (a): The activation of a fire alarm initiating device specified in ASME A17.1 section 2.27.3.2.1 at any elevator lobby, other than at the designated level, shall cause all elevators that serve that lobby, and any associated elevator of a group automatic operation, to be returned nonstop to the designated level.
SPS 318.1702(10)(b)2.
2. Substitute the following wording for the requirements in ASME A17.1 section 2.27.3.2.4 (a): The activation of a fire alarm initiating device specified in ASME A17.1 section 2.27.3.2.1(a) that is located in the elevator lobby at the designated level, shall cause all elevators serving that lobby to be recalled to the alternate level, unless Phase I emergency recall is in effect.
SPS 318.1702(10)(b)3.
3. These are department rules in addition to the requirements in ASME A17.1 section 2.27.8:
SPS 318.1702(10)(b)3.a.
a. An additional set of switch keys shall be kept in a lockable metal box mounted in a conspicuous location adjacent to the main elevator entrance or entrances at the designated level landing. Where a building has no fire command center and multiple lockable metal boxes, each box shall be openable by the same key. The box shall be openable only by the fire department, police department, licensed elevator inspector, and other authorized personnel. This does not prohibit additional keys from being placed in other approved locations.
SPS 318.1702(10)(b)3.b.
b. Where the elevator has a machine room, control room, or control space, the key box shall also contain a key to access the machine room, control room, or control space, and the key shall be labeled for its use. A label inside the key box shall provide directions to the location of the disconnects, including room number where applicable.
SPS 318.1702(10)(b)3.c.
c. Where the elevator has an inspection and test panel without a machine room, control room, or control space, the key box shall also contain the key for the lock used to secure the space, panel, or panels for the main disconnect, car light disconnect, and disconnects for any other elevator-utilization equipment. A label inside the key box shall provide directions to the location of the disconnects including room number where applicable.
SPS 318.1702(10)(b)4.
4. This is a department exception to the requirements in ASME A17.1 section 2.27.9: The department may approve an equivalent sign.
SPS 318.1702(10)(c)1.1. This is a department exception to the requirements in ASME A17.1 sections 2.27.3 to 2.27.9: The requirements in ASME A17.1 sections 2.27.3 to 2.27.9 apply to elevators serving one- or two-family dwellings as follows: where components addressed in those sections are installed, such components shall operate in accordance with those sections.
SPS 318.1702(10)(c)2.
2. Substitute the following wording for the requirements in ASME A17.1 section 2.27.1: The elevator shall be provided with a hard-wired telephone or a telephone utilizing wireless, cellular, or other technology capable of operating at all points of elevator travel. The telephone shall be available in the elevator, charged if battery powered, and operational any time the elevator is in use. If the telephone is not a hard-wired land line type, the elevator shall include a sign informing riders that a telephone is required to be present while operating the elevator.
SPS 318.1702 History
History: CR 14-020: cr.
Register August 2014 No. 704, eff. 9-1-14;
CR 19-118: cr. (1) (bm), renum. (10) (b) 1. to (10) (b) 1r., cr. (10) (b) 1g., am. (10) (b) 3. a., b., cr. (10) (b) 4., renum. (10) (c) to (10) (c) 1., cr. (10) (c) 2.
Register May 2020 No. 773, eff. 6-1-20.
SPS 318.1703(1)(1)
Hydraulic jacks. Substitute the following wording for the requirements in ASME A17.1 section 3.18.3.8.3(b):
SPS 318.1703(1)(a)
(a) The cylinder bottom and sides below the pit floor shall be completely surrounded by a protective material designed to withstand a static head of water from the ground level to the bottom of the cylinder, based on the manufacturer's rating of the material.
SPS 318.1703(1)(c)
(c) A means shall be provided between the material and cylinder to monitor the space for the entrance of water. The means to monitor shall comply with all of the following:
SPS 318.1703(1)(d)
(d) The space between the material, the means to monitor and the jack shall be sealed at or near the pit floor to prevent the entrance of water from the pit.
SPS 318.1703(1)(e)1.
1. Rigid, non-metallic material such as polyvinylchloride or high-density polyethylene, of a schedule that will withstand the installation process.
SPS 318.1703(1)(e)2.
2. Flexible material that is approved by the department. Monitoring for the entrance of ground water shall be performed according to the following schedule with findings recorded in the maintenance record:
SPS 318.1703(1)(f)
(f) If at any time water is found that cannot be explained by some type of accidental entry, the material shall be replaced within 6 months.
SPS 318.1703(2)
(2)
Operating devices and control equipment. Substitute the following informational note for the requirements in ASME A17.1 section 3.26.3.1.2:
Note: Under ICC/ANSI A117.1, as applied through the building code, the anti-creep device must maintain the car within 1/2 inch of the landing irrespective of the position of the hoistway door.
SPS 318.1703 History
History: CR 14-020: cr.
Register August 2014 No. 704, eff. 9-1-14;
CR 19-118: am. (1) (e) 2. b.
Register May 2020 No. 773, eff. 6-1-20.
SPS 318.1705(1)(1)
Limited-use, limited-application elevators. Substitute the following wording for the requirements in ASME A17.1 section 5.2.1.7: Equipment shall be permitted to be located in rooms containing other equipment essential for the operation of the building.
SPS 318.1705(2)
(2)
Hydraulic limited-use, limited-application elevators. This is a department exception to the requirements in ASME A17.1 section 5.2.2: Hydraulic limited-use, limited-application elevators are not required to conform to the requirements in ASME A17.1 section 5.2.1.19.
SPS 318.1705(3)(a)(a) This is a department rule in addition to the requirements in ASME A17.1 section 5.3: Machinery spaces, machine rooms, control spaces, and control rooms where provided shall conform to the requirements in ASME A17.1 section 5.2.1.7.
SPS 318.1705(3)(ag)
(ag) This is a department rule in addition to the requirements in ASME A17.1 section 5.3: A previously approved residential elevator installed to serve a commercial building may be replaced with a residential type elevator in the existing hoistway. A new installation permit is required.
SPS 318.1705(3)(ar)
(ar) This is a department rule in addition to the requirements in ASME A17.1 section 5.3.1.1.1: With the car at the lowest landing, the space above the car shall be guarded on all accessible sides by a partial enclosure extension or skirt. The extension shall be solid material or openwork that will reject a ball 1/2 inch diameter. The extension shall extend from the lower landing ceiling to 1 to 2 inches below the top edge of the car. Horizontal clearance between the car and the extension shall be 3/8 inch to 3/4 inch.
SPS 318.1705(3)(c)
(c) This is a department rule in addition to ASME A17.1 requirement 5.3.1.7.2: The vertical clearance between the hoistway door and the floor surface shall not exceed 3/8 inch.
SPS 318.1705(3)(cc)
(cc) This is a department rule in addition to the requirements in ASME A17.1 section 5.3.1.8.1:
SPS 318.1705(3)(cc)1.
1. The top of the car enclosure shall comply with the load requirements specified under ASME A17.1 section 2.14.1.6, except as specified in subd.
2. SPS 318.1705(3)(cc)2.
2. A car enclosure shall be permitted to have a top that is not load bearing provided the top of the car enclosure is not needed to be accessed to service, maintain, or inspect any part of the elevator equipment and contains a sign meeting ANSI Z535.4 or its equivalent indicating the car top is not load bearing.
SPS 318.1705(3)(cg)
(cg) This is a department rule in addition to the requirements in ASME A17.1 section 5.3.1.6.1: Ropes and chains passing through a wall outside the hoistway enclosure shall be enclosed with a solid or openwork enclosure. If the enclosure is openwork, the enclosure shall reject a ball 13 mm, or 0.5 in., in diameter. Means for inspection shall be provided. The openings may not be larger than is necessary to clear the suspension means.
SPS 318.1705(3)(cn)
(cn) The allowance in ASME A17.1 section 5.3.1.7.4 (a) is not included as part of this chapter.
SPS 318.1705(3)(cr)
(cr) This is a department rule in addition to the requirements in ASME A17.1 section 5.3.1.14: Where the hoistway ends above an occupiable area, the floor below the car and counterweight must have sufficient strength to withstand, without failure, the impact of the car with rated load and counterweight descending at 125% of rated speed or governor tripping speed if a governor is provided.
SPS 318.1705(3)(cw)
(cw) This is a department rule in addition to the requirements in ASME A17.1 section 5.3.1.16: Rotating parts located outside of the hoistway for private residence elevators shall be enclosed with a solid or openwork enclosure. If the enclosure is openwork, the enclosure shall reject a ball 13 mm, or 0.5 in., in diameter. Means for inspection shall be provided. The openings may not be larger than is necessary to clear the rotating parts.
SPS 318.1705(3)(d)
(d) The requirements in ASME A17.1 section 5.3.1.16.2(i)(2) are not included as part of this chapter.
SPS 318.1705(3)(e)
(e) Substitute the following wording for the requirements in A17.1 section 5.3.1.19: The elevator shall be provided with a hard-wired telephone or a telephone utilizing wireless, cellular, or other technology capable of operating at all points of elevator travel. The telephone shall be available in the elevator, charged if battery powered, and operational any time the elevator is in use. If the telephone is not a hard-wired land line type, the elevator shall include a sign informing riders that a telephone is required to be present while operating the elevator.
SPS 318.1705 Note
Note:
Accessible and Usable Buildings and Facilities, ICC A117.1, Section 409 for private residence elevators standards is applicable in commercial buildings, under the incorporation of the International Building Code
® in chs.
SPS 361 to
366.
SPS 318.1705(4)
(4)
Elevators used for construction. This is a department rule in addition to the requirements in ASME A17.1 section 5.10.1.21.2: All elevators shall have an assigned operator while in use.
SPS 318.1705 History
History: CR 14-020: cr.
Register August 2014 No. 704, eff. 9-1-14;
CR 19-118: cr. (3) (ag), (ar), renum. (3) (b) to (3) (cc) and, as renumbered, am. (3) (cc) 2., cr. (3) (c) 5., (cg), (cn), (cr),, (cw)
Register May 2020 No. 773, eff. 6-1-20; correction in (3) (c) 5. made under s. 35.17, Stats.,
Register May 2020 No. 773, eff. 5-1-20;
CR 20-057: renum. (3) (c) (intro.) to (3) (c) and am., r. (3) (c) 1. to 5. Register April 2021 No. 784. SPS 318.1707
SPS 318.1707 Dumbwaiter and Type B material lifts. SPS 318.1707(1)(1)
Power and hand dumbwaiters without automatic transfer devices. Substitute the following wording for the requirements in ASME A17.1 Part 7, Scope: This part applies to power dumbwaiters and Type B material lifts.
SPS 318.1707(2)
(2)
Hoistway-access doors. This is a department rule in addition to the requirements in ASME A17.1 section 7.1.11.5: Hoistway access door panels for power dumbwaiters shall be provided with an electric contact to remove power to the driving machine when the panel is not in the closed position.
SPS 318.1707(3)
(3)
Hoistway-door vision panels. Substitute the following wording for the requirements in ASME A17.l section 7.1.11.8: Vision panels shall be provided in hoistway doors where position indicators are not provided. Vision panels shall comply with the requirements in ASME A17.1 sections 2.11.7.1.2, 2.11.7.1.3, 2.11.7.1.4, and 2.11.7.1.6, and the total area of one or more vision panels in any hoistway door may not be less than 4 square inches and not more than 25 square inches.
SPS 318.1707 History
History: CR 14-020: cr.
Register August 2014 No. 704, eff. 9-1-14.
SPS 318.17081
SPS 318.17081 Security. This is a department rule in addition to the requirements in ASME A17.1 section 8.1: Key access for installations after June 1, 2020, as specified in this section, shall be verified by the department or agent municipality.
SPS 318.17081 History
History: CR 19-118: cr.
Register May 2020 No. 773, eff. 6-1-20.
SPS 318.17086
SPS 318.17086 Maintenance, repair, replacement, and testing. SPS 318.17086(1)(1)
Application of ASME A17.1 section 8.6. The introductory paragraph of ASME A17.1 section 8.6 is not included as part of this chapter.
SPS 318.17086(2)(a)(a) These are department rules in addition to the requirements in ASME A17.1 section 8.6.1.1.3:
SPS 318.17086(2)(a)1.
1. A new or updated maintenance control program, maintenance records, and wiring diagrams in electronic form shall be transferred to a paper copy of the documents by the installing or service contractor within 3 months of the associated maintenance, repair, replacement, or alteration.
SPS 318.17086(2)(a)2.
2. The maintenance control program, including any devices and procedures needed to meet ASME A17.1 section 8.6.1.2.1 (f), and the maintenance records and wiring diagrams are the property of the conveyance owner, not a conveyance installer or service company. They may be removed only with the permission of the owner.
SPS 318.17086(2)(a)3.
3. An additional set of electrical wiring diagrams may be securely located on the top of the car only if another complete set is located in a place that is accessible by the owner or the owner's agent.
SPS 318.17086(2)(b)
(b) Substitute the following wording for the requirements in ASME A17.1 section 8.6.1.2.1 (a): For new installations, the initial maintenance control program shall be provided by the equipment manufacturer. For existing equipment undergoing any alteration, repair, or replacement, the maintenance control program for the altered, repaired, or replaced components shall be provided by the person or firm performing the work. The maintenance control program shall be made available to elevator personnel at the scheduled time for service, tests, or inspection.
SPS 318.17086(2)(c)
(c) Substitute the following wording for the requirements in ASME A17.1 section 8.6.1.2.1 (d): A copy of the maintenance control program shall be located as follows:
SPS 318.17086(2)(c)1.
1. For a conveyance serving a commercial building and having a machine room, control room, or control space accessed directly from a building floor level or the roof, the program shall be located in that machine room, control room, or control space.
SPS 318.17086(2)(c)2.
2. For a conveyance serving a commercial building and having an inspection and test panel, the inside cover of the inspection and test panel shall provide instructions for locating the maintenance control program. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.
SPS 318.17086(2)(c)3.
3. For a conveyance serving a dwelling unit, either the maintenance control program shall be at the controller or the front of the controller shall provide instructions for locating the maintenance control program. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.
SPS 318.17086(2)(d)
(d) Substitute the following wording for the requirements in the introductory paragraph of ASME A17.1 section 8.6.1.2.2: The documents specified in ASME A17.1 sections 8.6.1.2.2 (a), (b), and (c), and par.
(e) shall be located as follows:
SPS 318.17086(2)(d)1.
1. For a conveyance serving a commercial building and having a machine room, control room, or control space accessed directly from a building floor level or the roof, the documents shall be located in that machine room, control room, or control space.
SPS 318.17086(2)(d)2.
2. For a conveyance serving a commercial building and having an inspection and test panel, the inside cover of the inspection and test panel shall provide instructions for locating the on-site documentation. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.
SPS 318.17086(2)(d)3.
3. For a conveyance serving a dwelling unit, either the on-site documentation shall be at the controller or the front of the controller shall provide instructions for locating the onsite documentation. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.
SPS 318.17086(2)(e)
(e) This is a department rule in addition to the requirements in ASME A17.1 section 8.6.1.2.2 (a), (b), and (c): Any plan approval letter, application form, and the plans issued under s.
SPS 318.1008.
SPS 318.17086(2)(f)
(f) This is a department rule in addition to the requirement in ASME A17.1 section 8.6.1.2.2 (c) (3): Written checkout procedures for two-way communication means shall be required for installations after June 1, 2020.
SPS 318.17086(2)(g)
(g) Substitute the following wording for the requirements in the introductory paragraph of ASME A17.1 section 8.6.1.4: Maintenance records shall document compliance with the requirements in ASME A17.1 section 8.6. The maintenance records shall be retained for the most recent 5 years minimum, or from the date of installation or adoption of this chapter edition. Existing maintenance records up to 5 years minimum shall be retained. Maintenance records shall be located as follows:
SPS 318.17086(2)(g)1.
1. For a conveyance serving a commercial building and having a machine room, control room, or control space accessed directly from a building floor level or the roof, the maintenance records shall be located in that machine room, control room, or control space.
SPS 318.17086(2)(g)2.
2. For a conveyance serving a commercial building and having an inspection and test panel, the inside cover of the inspection and test panel shall provide instructions for locating the maintenance records. Instructions shall be permanently legible with lettering not less than 1/8 in height.
SPS 318.17086(2)(g)3.
3. For a conveyance serving a dwelling unit, either the maintenance records shall be at the controller or the front of the controller shall provide instructions for locating the maintenance records. Instructions shall be permanently legible with lettering not less than 1/8 inch in height.